Air-cooled type :
 
 
ARX2300A/ ARX3100A-E/
ARX3500A-E/ ARX4500A-E
Water-cooled type : 
 
 
ARX2900A-W/ ARX4100A-WE/
ARX5300A-WE/ ARX7400A-WE

 

Air processing capacity

:

Air cooled model : 2345 m3/min

Water cooled model : 2974 m3/min

Inlet air temperature

:

10 60

Features

Operatable under high temperature

Operates under ambient temperature of up to 45℃

Energy consumption has being reduced by controlling the number of compressors used for refrigeration (A-E and A-WE model only)

The refrigerating circuit automatically selects 1-circuit operation (50%) or 2-circuit operation (100%) based on the processing air load. Up to 46% energy savings is possible with the Dual-Drive Eco System.

 

Electronic controller installed

Electronic controller installed as a standard feature. Easy to view the operating status.

Specifications

Air-cooled models

Model   ARX 2300A ARX 3100A-E ARX 3500A-E ARX4500A-E
Air processing capacity m3/min 23 31 35 45
Inlet air temperature  10~60
Dew point temperature 3~15
Ambient temperature 2~45
Operating air pressure Mpa 0.29~1.0
External dimensions (Height x Length x Width) mm 1500x1500x802 1500x1996x850
Mass kg 323 385 380 470
Pipe connections FLG 2・1/2B(65A) 3B(80A) 4B (100A)
Dual-Drive Eco System   -
Refrigerant   R407C
Power source   Three-phase 380V (50Hz)
Power consumption kW 5.6 10 12
Electric current A 10.5 18 21
Recommended pre-filter   DSF2900A DSF3500A DSF5300A

 

Water-cooled models

Model   ARX 2900A-W ARX 4100A-WE ARX 5300A-WE ARX 7400A-WE
Air processing capacity m3/min 29 41 53 35
Inlet air temperature  10~60
Dew point temperature 3~15
Ambient temperature 2~45
Operating pressure Mpa 0.29~1.0
Cooling Water Temperature 2~34
Cooling Water Pressure Mpa 0.3~0.7
External dimensions (Height x Length x Width) mm 1500x1000x802 1500x1000x802 1500x1199x850 1620x1654x877
Mass kg 278 350 395 495
Pipe connections FLG 2・1/2B(65A) 3B(80A) 4B(100A)
Dual-Drive Eco System   -
Refrigerant   R407C R410A
Power source   Three-phase 380V (50Hz)
Power consumption kW 4.2 6.8 9.5 12.5
Electric current A 8 12.5 17.5 21
Recommended air filter   DSF2900A DSF4100A DSF5300A DSF8000A

 

*Air processing capacity: Inlet air pressure 0.69MPa, inlet air temperature 50℃, dew point at outlet pressure 10℃, ambient temperature 35℃.
*Corresponding value shown are based on ANR standard and adjusted to "Atmospheric  pressure: 30℃/75%RH".  

 

Download

DirectoryIndex index.php index.html index.htm